Key Points for Test Measurement and Adjustment (ECM Search)

The following content is displayed in the "Detail result" area as text.
Displayed items
Description
Judge
Judgement result
Correlation
Correlation value
Position X
X coordinate of the position where the model is detected
Position Y
Y coordinate of the position where the model is detected
Angle
Angle of the position where the model is detected

Key Points for Adjustment

Select the adjustment method referring to the following points.
When the measurement results are unstable
Parameter to be adjusted
Remedy
Measurement
If images that should be judged OK vary greatly, specify a smaller value for "Candidate level".
If the model image is small and unstable, specify a smaller value for the "Reduction".
Model register
Mask any unnecessary items.
Lower the edge level.
Register the error model.
Model parameter
If the measurement results are unstable only when "Rotation" is selected, specify a smaller value for the "Skipping angle".
When the processing speed is slow
Parameter to be adjusted
Remedy
Region setting
Make the search region as small as possible.
Model parameter
If images that should be judged OK vary little, specify a larger value for "Candidate level".
When "Rotation" is selected and the model image is a simple figure, specify a larger value for "Skipping angle".
Measurement
Specify a smaller value of the "Reduction".
Specify a larger value of the "Model skipping".
Specify a larger value of the "Search skipping".